Pressure-purge bypass · XV-103 / RO-103
Fixed bore 6.430 mm · Cd 0.620 · sizing duty 40.00 Nm³/h · ΔP 2.0000 bar. Endpoint 1.0182 bara. Bypass gas discharged 5.5911 Nm³. 360 recorded blowdown snapshots. PCV-102 is excluded from bypass flow.
ṁ = Cd A P₁ / √(Rs T) × F(P₂/P₁, γ); choked below rcrit = [2/(γ+1)]^[γ/(γ−1)]. The isothermal vessel balance is dP/dt = −ṁ Rs T / V. Time is integrated along the falling pressure curve; O₂ mole fraction is unchanged by venting alone. Gas inventory closure uses the exact pressure change. No constant vent-flow demand is imposed during bypass blowdown.
NASA: compressible discharge and choking basis
Gas valve travel and capacity · whole recipe
| Valve / trim | Rated Cv | Peak required Cv | Peak travel | High travel / capacity limited | Controlling duty | Assessment |
|---|---|---|---|---|---|---|
| PCV-101 · Linear | 0.6300 | 0.3994 | 63.4% | 0.00 / 0.00 min | Step 1 · Inert / purge · 22.22 min 30.000 Nm³/h · 6.0133 → 3.0133 bara | Within capacity Below trim range: 72.59 min Finite-ΔP suggested Cv: 0.63 |
| PCV-102 · Linear | 1.6000 | 0.2618 | 16.4% | 0.00 / 0.00 min | Step 3 · Fill / charge · 28.38 min 0.864 Nm³/h · 1.0333 → 1.0133 bara | Within capacity Below trim range: 0.03 min Finite-ΔP suggested Cv: 0.4 |
Check every operation
| Valve | Step / operation | Peak Cv demand | Peak opening | High travel | Capacity limited | Below range |
|---|---|---|---|---|---|---|
| PCV-101 | 1 · Inert / purge | 0.3994 | 63.4% | 0.00 min | 0.00 min | 0.00 min |
| PCV-101 | 2 · Inert gas blanket | 0.3856 | 61.2% | 0.00 min | 0.00 min | 0.00 min |
| PCV-101 | 6 · Azeotropic phase withdrawal | 0.0020 | 0.3% | 0.00 min | 0.00 min | 21.36 min |
| PCV-101 | 7 · Cool down | 0.0039 | 0.6% | 0.00 min | 0.00 min | 51.23 min |
| PCV-101 | 8 · Discharge | 0.0308 | 4.9% | 0.00 min | 0.00 min | 0.00 min |
| PCV-102 | 3 · Fill / charge | 0.2618 | 16.4% | 0.00 min | 0.00 min | 0.00 min |
| PCV-102 | 4 · Fill / charge | 0.2270 | 14.2% | 0.00 min | 0.00 min | 0.00 min |
| PCV-102 | 5 · Heat up | 0.1591 | 9.9% | 0.00 min | 0.00 min | 0.03 min |
Checks use the existing imposed flow and pressure trajectory. High travel includes saturated demand; capacity-limited time is flagged interval duration. Below trim range means the requested flow is below rated Cv / rangeability; reliable throttling is not assumed. Recommendations apply to finite positive ΔP only and are not applied automatically.
Linear: Cv/Cv,rated = h. Equal percentage: Cv/Cv,rated = R^(h−1) over the controllable trim range. h is fractional travel. Zero demand closes the valve; below-range flow is flagged separately. Fixed xT, Fp = Z = 1. Vent gas approximates air plus selected inert gas; solvent vapour is excluded.